ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0060 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
OPERATING CONTROL SYSTEM SUB PANEL
J3
MEMORY MODULE
BATTERY
CONNECTOR
J5
LOWER TERMINAL BLOCK
PLC PROCESSOR MODULE
UPPER TERMINAL BLOCK
WITH MEMORY MODULE
PLC PROCESSOR
J4
OPERATING CONTROL
SUB-PANEL
Figure 3. PLC Processor Module and Memory Module Replacement.
5. Install a new processor and/or memory module as follows:
a. Connect the battery connector wire to J5 of the new processor.
b. Place the jumper on pins 2 and 3 of J4 of the processor.
c. Position the new memory module on J3 of the processor and press in place.
d. Position the processor in the 13-slot chassis and press into place.
e. Press the lower terminal block with its connected wiring onto the new processor module
and secure it with the two screws.
f. Press the upper terminal block with its connected wiring onto the new processor module.
g. Close the processor compartment door.
h. Close and secure the OCP instrument panel using the 14 screws.
0060 00-5