ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0062 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
CONTROL INSTRUMENTS
Configure a flow transmitter with its sensor as follows:
a. Press the MENU key to display a "MAIN MENU" screen.
b. If the "MAIN MENU/CONFIGURE" screen is not showing, use the up and down arrow
keys to display it.
c. Press the ENTER key to display Configure/Set Output.
d. Press the down arrow key until Configure/Language screen appears.
e. This setting is factory default set to English so no entry is required.
2. Configure the sensor:
a. Set the Multiplier (for displayed flow rate).
1) With the Configure/Language screen displayed, press down arrow key once
to display Configure/Sensor.
2) Press the ENTER key to display Sensor/Set Multiplier.
3) Press ENTER key again to display a screen like Set Multiplier/(x100).
4) Use the up and down arrow keys to select "x1".
5) With "x1" selected press ENTER key to enter selection.
b. Set the Decimal (for displayed flow rate).
1) With the Sensor/Set Multiplier screen displayed, press the down arrow key
once to display Sensor/Set Decimal.
2) Press the ENTER key to display a screen like Set Decimal/xxx.x. Use the up
and down arrow keys to select "xxx.x".
3) With "xxx.x" selected press the ENTER key to enter this selection.
c. Set the Filter Time.
1) With the Sensor/Set Decimal screen displayed, press the down arrow key
once to display Sensor/Set Filter.
2) Press the ENTER key to display a screen like Set Filter/0 Seconds.
3) Use the up and down arrow keys to adjust the displayed value to the desired
filter time of two (2) seconds and press the ENTER key to enter the value.
d. Select the Flow Units (for displayed flow rates).
1) With the Sensor/Set Filter screen displayed, press the down arrow key once
to display Sensor/Flow Units.
2) Press the ENTER key to display a screen like Flow Units/US GAL/MIN.
3) This setting is factory default to US GAL/MIN.
4) Press the ENTER key to accept this selection.
e. Select the Volume Units (for displayed volume).
1) With the Sensor/Flow Units screen displayed, press the down arrow key once
to display Sensor/Volume Units.
2) Press the ENTER key to display a screen like Volume Units/US GALLONS.
3) This setting is factory default to US GALLONS.
4) Press the ENTER key to accept this selection
f. Select the Enter Note (top line of Measurement screen).
1) With the Sensor/Volume Units Screen displayed, press the down arrow key
three times to display Sensor/Enter Note.
2) Press the ENTER key to display Enter Note/Flow.
3) This setting is factory default to Flow.
4) Press the ENTER key to accept this selection
0062 00-6