ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0062 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
CONTROL INSTRUMENTS
g. Select the Sensor Type.
1) With the Sensor/Enter Note screen displayed. Press the down key once to
display Sensor/Select Sensor.
2) Press the ENTER key to display a screen like Select Sensor/GLI PIPE
MOUNT.
3) Use the up and down arrow keys to select the type of sensor and mounting
arrangement for the transmitter according to the service as follows:
a) FT-101: GLI PIPE MOUNT
b) FT-401: GLI PVDF T
c) FT-501: GLI PVDF T
4) With the appropriate choice displayed, press the ENTER key to enter this
selection.
h. Set the Sensor Data.
NOTE
If a sensor is replaced, always enter the new sensor's related configuration data. If
the entered data does not match the sensor being used, measurement readings
will be inaccurate. After selecting/entering sensor type, the Sensor/Select Sensor
screen re-appears.
1) Press the down arrow key once to display Sensor/Set Sensor. Pressing the
ENTER key displays Set Sensor/Set Pipe ID (for FT-101) or Tee Size (for FT-
401 and FT-501)
2) For FT-101 only. With the Set Sensor/Set Pipe ID screen displayed, press
the ENTER key to display a screen like Set Pipe ID/(3.000 in.). Use the arrow
keys to adjust the display value to 3.314 in. and press ENTER key to enter the
value. (Right/left keys moves the curser. Up/down keys change the value of
the number at the curser.)
3) For FT-401 and FT-501. With the Set Sensor/Set Pipe ID screen displayed,
press the ENTER key to display a screen like Set Pipe ID/(3.000 in.). Use the
up/down arrow keys to adjust the display value to 2.0 in. and press ENTER key
to enter the value.
3. Configuring the Analog Output:
a. Set the Parameter (representation)
1) Press the MENU key to display a "MAIN MENU" screen.
2) If the MAIN MENU/Configure screen is not showing use the up and down
arrow keys to display it.
3) Press the ENTER key to display Configure/Set Output.
4) Press the ENTER key again to display Set Output/Set Parameter.
5) Press the ENTER key again to display a screen like Set Parameter/(Flow).
6) Use the up and down arrow keys to select desired choice "FLOW" press the
ENTER key to enter this selection.
b. Set the 4mA and 20mA Values (range expand)
1) With the Set Output/Set Parameter screen displayed, press the down arrow
key once to display Set Output/Set 4mA Value.
2) Press the ENTER key to display a screen like Set 4mA Value/(0.0 x 1GPM).
Use the arrow keys to set a displayed value of "ZERO" at which 4mA is
desired, and press the ENTER key to enter this value.
0062 00-7