TM 10-4610-310-14
0078 00
CORRECTIVE
MALFUNCTION
TEST/INSPECTION
ACTION
If voltage is present and no fault is
found at receptacle assembly,
1. Ensure that the distribution
Replace raw water
pump and cable is
pump if motor starter
serviceable.
module for the
2. Connect the dist. pump
distribution pump (M4)
cable to the raw water
trips
pump.
3. Turn on the dist. pump
switch
Inspect pump switch.
. Pump light is on but pump is not operating -
Inspect surge protector SP 2
Replace if voltage is
continued
present at the input
With power on, check for 240 VAC
and not at the output
at the input (between wires 75 and
74) and output (between wires 86
and 88).
Inspect motor controller module
Replace if voltage is
M1
present at the input
and not at the output
With power on, check for 240 VAC
at the input (between wires 60 and
61) and output (between wires 75
and 74).
cable wires from the
proper wire connections.
generator and
reconnect them
securely.
0078 00-2