TM 3-4230-209-10
Table 3-1. TROUBLESHOOTING (CONT)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. BURNER SPUTTERS OUT (CONT)
Step 5. Check HEATER RECEPTACLE AND SWITCH on pump unit for
loose power cable connection to be sure there is power.
Tighten power cable connection.
Step 6.
Check for loose plug or
receptacle on
the combustion air blower
motor.
Tighten loose connections.
Step 7.
Check for broken drive arms on
fuel pump, combustion magneto,
and fuel pump and ignition drive motor.
Step 8. Check for steam or water escaping from the gasket on the refrac-
tory-box end of the low pressure heating boiler,
Step 9. Check for a defective or worn fuel pump. With water heater oper-
ating in PURGE ON, visually inspect that fuel pump and ignition
drive motor is turning.
3-10