TM 5-4610-223-12
Table 4-2. Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
WATER PURIFICATION UNIT-Cont
Step 7.
Check for failure of feeder to prime.
Prime by hand (fig. 2-17).
11. SLUDGE CONCENTRATOR TANK FAILS TO CONTROL SLURRY BLANKET.
Step 1.
Check for slurry blanket rising too rapidly.
Reduce agitator speed.
Step 2.
Check for slurry blanket rising above circular baffle.
Adjust the valve DV-21 (fig. 2-13).
Step 3.
Check for valves not correctly positioned.
Reposition valves CV-16 and CV-17, and DV-21 (fig. 2-19 and 2-13).
12. WET WELL FAILS TO DELIVER ENOUGH CLEAR WATER.
Step 1.
Check for valves not positioned correctly.
Reposition the valves CV-17 and DV-25 (fig. 2-19 and 2-13).
13. DIATOMITE FILTER PUMP WILL NOT DELIVER WATER .
Step 1.
Check for valves not positioned correctly.
Reposition valves CV-36 and CV-34 (fig. 4-58).
Step 2.
Air leaks on suction side of pump.
Tighten connections and stop all leaks.
Step 3.
Check for sheared impeller key.
Report trouble to direct support maintenance.
4-31