2.2
Edit Switch Parameters
Switches have only four (4) parameters that are editable. These are:
Switch Active - When set to "0", the switch is active. When set to "1", the switch has been deactivated,
and the switch is displayed as a borderless label.
Alarm Delay - same as sensors.
Normal open/closed - Each switch can be edited to set the normal state, the state in which it will not
alarm. (0 = closed, 1 = open).
Alarm Lockout - same as sensors.
2.3
Edit Totalizers
A totalizer is a display of up to eight digits with no bar. it is an accumulation of pulses or hours of operation.
Totalizer Active When set to "o", the totalizer is active and will count. When set to "1", the totalizer will
be deactivated, and the display will be replaced by "X"'s.
Schedule Log Entry A totalizer can be individually enabled to be logged on the Printer during a
schedule log.
Counts/Units Used to set the number of pulses to be counted as 1 unit. For example, a counts/unit
value of 4 would mean that every 4th pulse would be totalized.
Preset A preset total of up to 8 digits may be entered as a starting point.
Type indicates whether the channel is a direct totalizer, a co-channel of a rate channel, or an engine
timer. Do not edit. Value is assigned at factory before installation.
Range Unused Calibration Unused
2nd Totalizer Totalization will simultaneously occur on this co-channel. An example of such an
application would be total fuel consumed and trip fuel consumed.
Section 3 - Page 5