TM 55-1930-209-14&P-19
Table 9-3. Preventive Maintenance Checks and Services for Electrical Power Systems(Continued)
B - Before
D - During
A - After
H - Hourly Interval
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A
H
AS NECESSARY
10 hrs
b. Check that engine crankcase oil is
between ADD and FULL marks on dip-
stick. If necessary, add oil at oil fill
located above oil dipstick on accessory
end of engine. Oil must meet engine ser-
vice classification CD(MIL-L-2104) or
CD/TO-2. See table below for engine
crankcase lubrication. Diesel engines on
board use 15W40 crankcase lubricant for
normal temperatures. Use SAE40 if tem-
peratures consistantly exceed 120°F.
10 hrs
c. Clean air cleaner element by performing
the following:
1) On air cleaner, unlatch two rackover
latches. Remove air cleaner cover and
filter element.
2) Cover turbocharger intake opening
located inside the air cleaner body.
3) Clean inside of air cleaner cover and
body with clean cloth and solvent.
Wipe dry.
9-9