TM 55-1930-209-14&P-19Table 9-3. Preventive Maintenance Checks and Services for Electrical Power Systems(Continued)B - BeforeD - DuringA - AfterH - Hourly IntervalINTERVALITEMPROCEDURESEQUIPMENTITEMTO BECHECK FOR AND HAVEIS NOT READY/NO.INSPECTEDREPAIRED OR ADJUSTEDAVAILABLE IFB D AHAS NECESSARYj. From switchboard, with generator loadapplied, check that battery chargerammeter indicates batteries beingcharged. Report failures to shift leader orbargemaster.10 hrsk. Drain water and sediment from fuel/water separator (on barges 2 and 3 only).I. Check that seawater is available for heatSeawater is notexchanger. Make sure both stern seawa-available for heatter strainer baskets are clean and opera-exchanger.ble.250 hrsg. Change crankcase oil and oil filter ele-ment by performing the following:1) Run engine until oil is hot. Turn offengine by following procedures:(a) Make sure electrical load has beentransferred to other generatorsets and that applicable circuitbreaker (P1 for SSG 1 or P2 forSSG 2) is open (OFF).(b) Operate engine at idle speed for 5minutes.(c) At engine, push engine START/STOP switch to STOP.2) Redtag affected SSG on switchboardpanel indicating, "WARNING - DONOT ACTIVATE. REPAIRS BEINGMADE."3) Open bilge drain valve (BD16 for SSG1, BD17 for SSG 2) below oil dipstick.Drain at least 1 pint of oil into cleancontainer for Army Oil Analysis Pro-gram (AOAP). Close valve. Sendmarked oil sample to IDS or IGS unitfor analysis.9-12