TM 10-4610-232-34
(2) Install tie wraps (TM 10-4610-232-12, para. 4-10).
(3) Connect cable at the main control panel (para. 2-21).
b. Refer to sheet 3 and install cable (W70) as follows:
(1) Open the CO monitor door and connect cable into the CO monitor (para. 2-56).
(2) Install tie wraps (TM 10-4610-232-12, para. 4-10).
(3) Connect cable at the 24 VDC power supply (para. 2-53).
c. Refer to View D on sheets 2 and 4 and install cables (W30, W31 and W32) as follows:
(1) Install sensor (3) and gasket (4) into pipe (5) and secure with eight washers (2) and capscrews (1).
(2) Install tie wraps (TM 10-4910-232-12, para. 4-10).
(3) Connect cables (W30, W31 and W32) at the main control panel (para. 2-21).
d. Refer to sheet 2 and connect CO monitor cable (W69) as follows:
(1) Open the CO monitor door and install cable onto the CO monitor (para. 2-56).
(2) Install tie wraps (TM 10-4610-232-12, para. 4-10).
(3) Connect cable (W69) at the main control panel (para. 2-21).
e. Refer to sheet 1 and install cables (W38 and W39) as follows.
(1) Connect cables at the main control panel (para. 2-21).
(2) Route the cables through the opening in the wall of the ROWPU and screw the cables into the cannon plug
connectors on the MOV junction box.
(3) Refer to View C and install the cables in the cable clamps as follows:
(a) Place clamp (6) on the cable and place the clamp in channel (7).
(b) Install screw (1), washer (2), washer (5), Iockwasher (4) and nut (3).
(4) Install tie wraps (TM 10-4610-232-12, para. 4-10).
f. Refer to sheet 1 and install cable (W1) as follows:
(1) Starting from outside the ROWPU, slide nut (1, View B) and seal (2) on the cable to be installed.
(2) Install straight fitting (4) with seal ring (5) in place in the wall of the ROWPU.
(3) Push the cable through straight fitting (4) and install conduit nut (3) on the cable.
(4) Push the cable far enough into the ROWPU to be sure the cable can be connected to the main control panel.
(5) Tighten conduit nut (3) and nut (1).
(6) Slide another nut (1) and seal (2) on the control panel end of the cable and connect the cable to the main control
panel (para. 2-21).
(7) Connect power leads (W1) to generator as follows:
(a) Connect lead L1 to stud L1.
(b) Connect lead L2 to stud L2.
(c) Connect lead L3 to stud L3.
(d) Connect lead L0 to stud L0.
2-108