TM 10-4610-239-24
TM 08580B-24/3
ASSEMBLY. (Cont)
CAUTION
Unequal torque on any end cap nut can result in damage to the
pressure tube.
m. Install filter elements. (Refer to TM 10-4610-239-10).
n. Install concentrate port (17) into end plate (4).
o. Install new retaining ring (16) on concentrate port (17).
p. Install O-ring (15) and adapter (14) on permeate port (8).
q. Install O-rings (12) and (13) on end plug (5).
NOTE
The two O-rings in the end connector have different outside
diameters. Feel inside connector to find the large and small
inside diameter ends. Install large O-ring in large end of end
connector. Install small O--ring in small end of end connector.
r.
Install O-rings (10) and (11) in connector (9).
s.
Install end connector (9) on permeate port (8).
t.
Insert permeate port (8) through end plug (5), end plate (4) and install new retaining ring (7) on permeate
port (8).
u. Install end connector (9) on permeate port (8).
NOTE
Small inside diameter end of end connector goes in permeate
port.
v.
Install capscrews (6) into end plate (4) and end plug (5).
w. Install end plate (4) and end plug (5) onto pressure tubes (3).
2-218