TM 10-4610-310-14
0010 00
CHEMICAL INJECTION CONTINUED
8. The injection point for the Hypochlorite is on the product water outlet piping on the chemical module.
9. No connection is necessary from chemical pump P7 to the injection point on the product water out piping.
See Figure 7.
PRODUCT
HTH
WATER
INJECTION
OUTLET
POINT
PIPING
6-FOOT
ANISCALANT
HOSE
INJECTION PUMP P5
COAGULANT/BISULFITE
INJECTION PUMP P6
HYPOCHLORITE
INJECTION PUMP P7
Figure 7. Hypochlorite Injection Port on Chemical module.
CHEMICAL INJECTION PUMP OPERATION
CAUTION
Adjustments to the chemical injection pumps' stroke setting must only be done while the
pump is in operation. Any attempt to adjust the stroke setting while the pump is not in
operation, will cause damage to the pump.
1. Turn the CHEMICAL PUMPS selector switch on the control panel to the HAND position.