TM 10-4610-310-14
0095 00
AIR SHUTOFF ASSEMBLY REMOVAL - continued
5. Unthread the Schrader valve (1), drain valve (15), tee (14) and nipple (13), if necessary, by unthreading them
counter clockwise.
6. Remove the air tank from the module by removing bolts (16), washers (17), bushing (18), rubber rings (19)
and nuts (20).
AIR SHUTOFF ASSEMBLY INSTALLATION
1. Refer to Figure 4 for this procedure section.
2. Install the air tank to the module by using bolts (16), washers (17), bushing (18), rubber rings (19) and nuts
(20).
3. Install the Schrader valve (1), drain valve (15), tee (14) and nipple (13), if necessary, by threading them
clockwise.
4. Install the threaded nipple (6), gauge (5), safety pop valve (4), cross (3), and nipple (12), if necessary, by
threading them clockwise.
5. Install the threaded nipples (6) to solenoid valve (7) and shutoff valve (11), if necessary.
6. Install the solenoid valve (7) to the threaded nipple (6).
AIR TANK SOLENOID COIL INSTALLATION
1. Refer to Figure 3 for this procedure section.
2. Slide the coil (2) on the solenoid valve (1) and secure with spring washer (3) and nut (4). See Figure 3.
3. Install vent assembly (5) on the solenoid valve (1).
4. Feed the wires (28 and 3) through the electrical conduit and connect it in high-pressure pump module junction
box, if removed.
5. Ensure that the wires are connected to same slot on the terminal block for wire 28 and 3 from the control
panel.
6. Thread the conduit on the coil, if removed.
AIR FILTER ASSEMBLY INSTALLATION
1. Refer to Figure 2 for this procedure section.
2. Install gasket (2 b) on the intake manifold.
3. Slide the shutoff valve on the studs.
4. Install the gasket (2 a).
5. Install the filter housing (9) on the studs and secure with bolt (11), nuts (5), lock washers (4) and washers (3).
6. Install the filter element (6) and cover (8) and secure with wing nut (7).
END OF WORK PACKAGE
0095 00-4