TM 10-4320-317-13
(12) Locate inlet (1, Figure 2-24) and outlet (2) ports of hypochlorination unit. Unscrew plastic dust caps from both
ports. Store caps for later use.
(13) Wrap anti-seize tape (Item 10, Appendix E) around threads on nipple (3). Screw nipple (3) into inlet (1) port on
hypochlorination unit.
(14) Screw female quick-is connect coupling half (4) onto nipple (3).
(15) Push cam arms on female quick-disconnect coupling half (4) forward to open position.
(16) Connect male end of reducer (5) to female quick-disconnect coupling half (4). Close cam arms.
(17) Push cam arms on female end of reducer (5) to open position.
(18) Connect 2 in. X 10 ft hose (6) from 125 GPM pump to female end of reducer (5). Close cam arms.
Figure 2-24. Hypochlorination Unit
NOTE
The anti-seizing tape is to be wrapped in the same direction as the pipe threads.
2-45