ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0063 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
POWER DISTRIBUTION SYSTEM
CIRCUIT BREAKERS (10)
DIN RAIL HOLDING CLIP
POWER DISTRIBUTION PANEL
Figure 2. Circuit Breaker Replacement.
2. Install a new circuit breaker as follows:
a. Position the new circuit breaker on the DIN rail and carefully press the circuit breaker in
place.
b. Attach the wires to the screw connections in accordance to the wire tags.
c. Tighten the screw connections to secure the wires.
d. Remove the wire tags if necessary.
e. Reinstall the wire duct covers.
f. Close the power distribution panel.
GFI Module Replacement:
Parts (TM 10-610-309-24P):
GFI Module, 4 pole, 300ma
GFI Module, 2 pole, 30ma
Equipment Condition:
TWPS in Standby Shutdown Without Draining Down
Army TWPS: Generator off and TWPS main breaker off
Marine Corps TWPS: TWPS disconnected from power source
0063 00-5