ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0066 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
GENERAL MAINTENANCE
Pipe Coupling Replacement:
Parts (TM 10-4610-309-24P):
Pipe Coupling
Materials:
Clean, dry lint-free rags (WP 0079, Table 1, item 33)
Corrosion preventive compound (WP 0079, Table 1, item 17)
Equipment Condition:
TWPS in Standby Shutdown with Drain-Down
Replace a pipe coupling (see Figure 17).
1. Make sure the TWPS is in Standby Shutdown with Drain-Down. Refer to WP 0017.
2. Remove the pipe coupling as follows:
a. Remove the nuts and bolts that secure the clamps to the pipe joint at both ends of the
pipe joint. Remove the clamps and set aside.
b. With a screw driver and hammer, tap the gasket retainers loose from the gaskets at both
ends. Push the pipe joint and gasket back onto one of the pipes until it clears the end of
the other pipe.
c. Remove pipe support clamps and loosen other connections as needed to free one or
both pipes to move or rotate enough to move the ends clear of each other. Remove the
gaskets, gasket retainers and pipe joint from the pipes.
PIPE JOINT
GRIPPERS (2)
NUT
GASKET
BOLT
PIPE END
GASKET RETAINER
CLAMP
Figure 17. Pipe Coupling Replacement.
3. Clean the pipe ends with a clean, lint-free rag and inspect for rust, corrosion and damage that
would prevent the pipe coupling from sealing.
4. Install a new pipe coupling as follows:
a. Insert the two gripper sections into the inner diameter of a gasket.
b. Insert the gasket into the gasket retainer.
c. Slide the retainer, gasket, and gripper assembly over one of the two pipe ends (retainer
side first).