GENERATOR GROUNDING - continued
CAUTION
If any generator other than the 3 kW TQG is used, a qualified electrical technician must approve and supervise
the connection and operation of the generator.
Connect the main power cord (white) from the control module to the 3kW TQG. Ensure that the wires are
5.
secured by tightening the split bolt firmly.
GROUNDING CABLE
Figure 2. 3kW TQG Set Connections.
L1 = Black wire
N = White wire
L2 = Red wire
GND = Ground wire (green)
CAUTION
Always inspect electrical power cables for damage before energizing the LWP. Damage to
equipment may result.
FUELING 3KW TACTICAL QUIET GENERATOR SET
WARNING
Refuel in a well-ventilated space with the 3kW TQG set diesel engine stopped. Do not
smoke or allow sparks/flames where engine is refueled. Ensure filler cap is secured after
refueling. If any fuel is spilled while refueling, make sure area is dry before restarting
engine. Never use any starting aids such as ether, gasoline, or other starting liquids as this
may cause severe damage to the engine. Injury or death could result.
1. Check the lubricating oil and diesel fuel tank levels in the 3kW TQG set according to TM 9-6115-639-13.
2. Replenish the oil and fuel as necessary.
SETTLING TANK SETUP
1. Perform all before PMCS for the hoses and tanks, control module, raw water service pump, and ground rod.
2. Place the settling tank in a suitable, level location where it will not roll or move as it fills up with water.