TM 10-4610-239-24
TM 08580B-24/3
REMOVAL.
WARNING
High voltages in this equipment can cause serious injury or death. Be certain
that all power is removed before performing maintenance.
The junction box assembly is heavy/difficult to handle. Two people are
needed to lift it to prevent personal injury or damage to the equipment.
a. Position junction box assembly (4), turn 13 rotary fasteners (1), and lower junction boxcover (2).
b. Support junction box assembly (4) and install nine screws (21), new lockwashers (20), and nuts (19).
Do not tighten screws.
c.
Remove four screws (12) and flat washers (13) and tilt circuit breaker plate (15) forward.
d. Align junction box and install three screws (18), new lockwashers (17), and nuts (16).
e. Tighten 12 screws (18) and (21).
f.
Position circuit breaker plate (15) on four standoffs (14) and install four screws (12) and flat washers
(13).
NOTE
There are seven cables with connectors which attach to receptacles mounted
on the junction box assembly. All are installed the same. One is shown.
g. Install cable connector (5) on receptacle (6).
NOTE
There are five electrical cables connected to terminals in the junction box
assembly. All are installed the same. One is shown.
i.
Close junction box cover (2) and turn 13 rotary fasteners (1) to secure.
j.
Install wire lug (10), flat washer (9), new lockwasher (8), and nut (7) on ground stud (11).
3-185