f. Move Motor-Driven Product Water Distribution Pump Skid P-7 roughly into place.
g. Place the pump skid on solid footing and as nearly level as possible.
2. Connect the hoses as follows:
WARNING
Health hazard. Do not attempt to use product water hoses to handle raw water or
raw water hoses to handle product water. When installed with the proper adaptors
as directed, the hoses cannot be interchanged. Failure to observe this warning
and mixing hoses could cause contamination of water resulting in serious illness.
a. Collect the following adaptors, hoses, and dispensing nozzles:
1) Four 1 in. x 10 ft, blue-banded product water suction hoses.
2) Adaptor A-15.
3) Adaptor A-07.
4) One 2 in. x 5 ft., blue-banded product water suction hose with male couplings at
each end.
5) One 2 in. x 5 ft., blue-banded product water suction hose with female couplings
at each end.
6) Pump outlet tee Adaptor A-08.
7) Two 2 in. x 65 ft., blue-banded product water distribution discharge hoses.
8) Two Dispensing Nozzles V-523A and V-523B.
b. Inspect the gaskets in the female ends of the hoses and adaptors. Replace any
damaged or missing gaskets.
c. Connect the four 1 in. x 10 ft., blue-banded product water suction hoses to each other.
d. Remove the plug from the TWPS product water discharge outlet hose and connect the
assembled blue-banded product water suction hoses to the discharge hose. Put the plug
in Storage Box #3.
e. Connect Adaptor A-15 to an outside inlet (not an inlet between tanks) of the product
water distribution tank that is closest to the TWPS product water outlet.
WARNING
Health hazard. Do not connect the product water hose from the TWPS to Adaptor
A-15 at the product water distribution tank at this time. Initial product water
discharge from the product water outlet of the TWPS will not be of adequate purity.
Product water is not discharged into the product water tanks until after clean
product water flow is established. Failure to observe this warning could cause
f.
Connect the male end of the straight section of Adaptor A-07 directly to the female outlet
of one of the distribution tanks.
g. Connect the male-male 2 in. x 5 ft., blue-banded product water suction hose to the other
end of the straight section of Adaptor A-07.
h. Connect the other end of the 2 in. x 5 ft. suction hose to the outlet of the other distribution
tank.