TACTICAL WATER PURIFICATION SYSTEM (TWPS)
PREPARATION FOR USE AND INSTALLATION INSTRUCTIONS
SET-UP OPERATION UNDER USUAL CONDITIONS
c.
Spread the tanks out to their final shape and eliminate any ridges in the bottoms.
Position the tanks about 6 ft. apart with the connections facing each other.
d. Pull the tank inlet and outlet connections out away from the tank bottoms so that they will
be clear when the tanks are filled.
e. Move Diesel-Driven Product Water Distribution Pump Skid P-8 roughly into place.
1) Place the pump skid on solid footing and as nearly level as possible.
2) Place an absorbent pad under the diesel-driven pump skid for environmental
protection in the event of a fuel spill.
A-08
2 X 65 D-HOSE
A-15
P-8
NOZZLE V-523D
2 X 5 S-HOSE
T-6
T-7
2 X 5 S-HOSE
T-5
TWPS
A-07
Figure 13. Extended Product Water Distribution System Equipment Deployment
2. Connect the hoses as follows:
WARNING
Health hazard. Do not attempt to use product water hoses to handle raw water or
raw water hoses to handle product water. When installed with the proper adaptors
as directed, the hoses cannot be interchanged. Failure to observe this warning
and mixing hoses could cause contamination of water resulting in serious illness.
0007 00-22