TM 10-4610-310-14
0038 00
PROCEDURE - continued
9. Connect the backwash pump suction hose to the cleaning tank outlet. See Figure 1.
WARNING
When using any chemicals, follow all safety regulations. Always wear eye protection as a minimum.
When handling corrosive chemicals wear goggles and protective clothing and gloves. Failure to follow
this warning may result in injury or death to personnel.
10. Add 390 ml of Sodium Hypochlorite to the cleaning tank product water. Mix well with paddle.
11. Disconnect the backwash inlet hose from the UF module.
12. Open cleaning tank drain valve.
13. Keep the hose disconnected until the cleaning solution flows from the cleaning tank through the backwash
service pump.
14. Reconnect the backwash inlet hose to the UF module. See Figure 4 for cleaning diagram.
1
Cleaning Tank Outlet
2
Backwash Inlet
3
UF Reject
4
UF Inlet
Figure 4. Maintenance Cleaning Diagram.