RO PRESSURE VESSEL INSTALLATION
Properly position replacement pressure vessel in RO element module frame.
1.
Secure pressure vessel assembly to RO element module as follows:
2.
a.
Verify that victaulic adapters of pressure vessel assemblies line up.
b.
Install U-bolt, two nuts, and two washers. Do not tighten. See Figure 2.
c.
Install U-bolt, two nuts, and two washers at opposite end of pressure vessel assembly.
3. Inspect victaulic adapter gasket for cuts, gouges and cracking that would prevent a watertight seal. Replace
gasket when defective.
4. Slide gasket over victaulic adapters
5. Install coupling clamp over victaulic adapters and gaskets.
6. Secure in place with two bolts and two nuts. Tighten securely.
7. Install RO element in pressure vessel assembly. See WP 0045 00.
8. Install front and rear end caps with plugs and O-rings. Secure in place with retaining ring. See WP 0045 00.
9. Apply anti-seize tape to threads of 3-way sampling valve.
10. Install 3-way sampling valve onto end cap. Tighten securely.
11. Secure polyethylene tubes with nuts to 3-way sampling valves
12. Tighten nuts.
RO REJECT PIPING INSTALLATION
1. Refer to Figure 3 for this procedure section.
2. Reassemble RO reject valve (8) if necessary. See WP 0129 00.
3. Install adapter (3), male camlock (2) and dust cap (1) if necessary.
4. Install the U-bolts (6) and secure with nuts (5) and washers (4). Place the piping on the module.
5. Install tubing on the elbow (9).
6. Install the victaulic clamp to attach the reject piping to the tail end of vessel number 7.
END OF WORK PACKAGE