TM 10-4610-310-14
0085 00
UF TANK INLET PIPING - continued
2.
Remove the coil from the solenoid valve (13). See WP 0088 00.
3.
Loosen union (1) and remove screws (10), locknuts (11) and washers (12) from solenoid valve (13).
4.
Disconnect the hose from the fitting (6).
5.
Remove the flow controller (2), nipple (3), flow indicator (4) filtrate valve (5) and fitting (6) from the piping
only if necessary.
LEVEL SWITCH PIPING
1. Loosen the union (1). Remove nuts (6) and washers (5) from the U-bolt (3).
Figure 4. Level Switch Piping.
2. Remove hose from the elbow (4). Remove level switch (7) from the holder (2) only if necessary.
BACKWASH INLET PIPING
1. Loosen unions (1,2 and 3). Remove tubing from tee fitting (7).
Figure 5. Backwash Inlet Piping.
2. Remove nuts (10) and washers (11) from the U-bolts. Remove the U-bolts.
3. Remove check valve (5), flow control valve (6), female camlock (8) and dust plug (9) only if necessary.
4. Remove support washer (12) and 30-mesh screen (13) if necessary. Discard screen (13).